Need help? Talk to an expert
Free +91-22-26731904
et viewet diag

Software Et-view Et-diag

Features

Visualisation:
  • Individual text to identify each measuring point (channel)
  • Indications for operation, alarms, transmitter fault
  • Measuring values with physical unit and gas
  • Indications for ET-8D-status operation, maintenance, fault and data transmission
  • Cycle time for actualization configurable
  • Visualisation of all connected control units simultaneously
Data logging:
  • Capacity depends on hard disc only
  • Recorded data includes time stamp and all of the visualized data
Data loop through:
  • Data transmission to external periphery, e. g. PLC, possible
Diagram:
  • x-y-diagrams (up to two y-axis, scalable)
  • Basic time intervals: day or month
  • Zoom functions
  • Options: Copy, save and print of the displayed diagram
Control units:
  • Up to 16 control units ET-8D or ET-4D2

System Requirements

Personal Computer (Operating System):
  • Microsoft Windows 2000/XP/Vista™/Windows 7
Communication (Control Unit <-> PC):
  • RS 485 interface (or RS 485-adapter for RS232- or USB-ports)
Control units:
  • Suitable software version (ask ExTox for information)
  • Configuration of RS 485-address on PCB of the control unit (see operating manual)
Transmission parameters:
  • 9600 Baud, 8 Data bits, 1 Stop bit, no parity
Cabling:
  • twisted pair, shielded